Low Power Company, Inc. LP-4290 SPECpower_ssj2008 = Invalid overall ssj_ops/watt
Test Sponsor: Low Power Company, Inc. SPEC License #: 0 Test Method: Single Node
Tested By: Low Power Company, Inc. Test Location: Mountain View, CA Test Date: Apr 14, 2017
Hardware Availability: March 2017 Software Availability: Mar-2017 Publication: Unpublished
System Source: Low Power Company, Inc. System Designation: LP-4290-8H Power Provisioning: Line-powered
WARNING: PTDaemon 1.8.0-3505e615-20160120 is over 12 months old. Check http://www.spec.org/power/docs/SPECpower-Device_List.html to determine if a newer version is available. (see Run Rules Section 1.1)
WARNING: PTDaemon 1.8.0-3505e615-20160120 is over 12 months old. Check http://www.spec.org/power/docs/SPECpower-Device_List.html to determine if a newer version is available. (see Run Rules Section 1.1)
INVALID: Temperature Sensor "temp1" not accepted (see Run Rules Section 2.13.4)
WARNING: Autoranging was enabled for current on Power Analyzer "pwr1". The use of autoranging is discouraged. (see Run Rules Section 2.13.2)
WARNING: Autoranging was enabled for voltage on Power Analyzer "pwr1". The use of autoranging is discouraged. (see Run Rules Section 2.13.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 0, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 236 samples with unknown uncertainty out of 236 total samples (100.0%) in interval 1, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 235 samples with unknown uncertainty out of 235 total samples (100.0%) in interval 2, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 239 samples with unknown uncertainty out of 239 total samples (100.0%) in interval 3, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 238 samples with unknown uncertainty out of 238 total samples (100.0%) in interval 4, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 5, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 6, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 236 samples with unknown uncertainty out of 236 total samples (100.0%) in interval 7, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 235 samples with unknown uncertainty out of 235 total samples (100.0%) in interval 8, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 9, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 238 samples with unknown uncertainty out of 238 total samples (100.0%) in interval 10, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 11, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 12, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 13, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
Benchmark Results Summary
Target Load Average Active Power (W) Minimum Ambient Temperature (°C)
Calibration 1 48.6 21.2
Calibration 2 49.1 21.2
Calibration 3 49.3 21.2
100% 49.3 21.2
90% 50.8 21.2
80% 50.2 21.2
70% 48.5 21.2
60% 45.5 21.2
50% 41.0 21.2
40% 35.4 21.2
30% 30.1 21.2
20% 24.2 21.2
10% 19.5 21.2
Active Idle 15.2 21.2
Graph of power and temperature
Measurement Devices
Power Analyzer pwr1
Hardware Vendor: Hioki
Model: 3334
Serial Number: 150526689
Connectivity: USB
Input Connection: Default
Metrology Institute: NIST
Accredited by: Hioki
Calibration Label: Unknown
Date of Calibration: Unknown
PTDaemon Host System: same as CCS
PTDaemon Host OS: same as CCS
PTDaemon Version: 1.8.0-3505e615-20160120
Setup Description: Unknown
Temperature Sensor temp1
Hardware Vendor: Digi
Model: Watchport H/T Sensor
Driver Version: io_ti 3.16.0-4-amd64
Connectivity: USB
PTDaemon Host System: same as CCS
PTDaemon Host OS: same as CCS
Setup Description: 5mm in front of SUT
Notes
None
Power Details for Device pwr1
Target Load Voltage (V) Current (A) Avg Power Factor Avg Active Power (W) Power Measurement Uncertainty (%)
Avg Range Avg Range
Calibration 1 120 auto 0.414 auto 0.983 48.6 --
Calibration 2 119 auto 0.419 auto 0.984 49.1 --
Calibration 3 119 auto 0.420 auto 0.984 49.3 --
100% 119 auto 0.421 auto 0.984 49.3 --
90% 119 auto 0.440 auto 0.975 50.8 --
80% 118 auto 0.441 auto 0.963 50.2 --
70% 120 auto 0.426 auto 0.951 48.5 --
60% 120 auto 0.407 auto 0.935 45.5 --
50% 119 auto 0.374 auto 0.919 41.0 --
40% 120 auto 0.328 auto 0.905 35.4 --
30% 120 auto 0.283 auto 0.895 30.1 --
20% 119 auto 0.229 auto 0.893 24.2 --
10% 120 auto 0.183 auto 0.889 19.5 --
Active Idle 120 auto 0.140 auto 0.906 15.2 --
Power details for pwr1