Low Power Company, Inc. LP-4290 SPECpower_ssj2008 = Invalid overall ssj_ops/watt
Test Sponsor: Low Power Company, Inc. SPEC License #: 0 Test Method: Single Node
Tested By: Low Power Company, Inc. Test Location: Mountain View, CA Test Date: Apr 18, 2017
Hardware Availability: March 2017 Software Availability: Mar-2017 Publication: Unpublished
System Source: Low Power Company, Inc. System Designation: LP-4290-8H Power Provisioning: Line-powered
WARNING: PTDaemon 1.8.0-3505e615-20160120 is over 12 months old. Check http://www.spec.org/power/docs/SPECpower-Device_List.html to determine if a newer version is available. (see Run Rules Section 1.1)
WARNING: PTDaemon 1.8.0-3505e615-20160120 is over 12 months old. Check http://www.spec.org/power/docs/SPECpower-Device_List.html to determine if a newer version is available. (see Run Rules Section 1.1)
WARNING: Autoranging was enabled for current on Power Analyzer "pwr1". The use of autoranging is discouraged. (see Run Rules Section 2.13.2)
WARNING: Autoranging was enabled for voltage on Power Analyzer "pwr1". The use of autoranging is discouraged. (see Run Rules Section 2.13.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 0, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 236 samples with unknown uncertainty out of 236 total samples (100.0%) in interval 1, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 236 samples with unknown uncertainty out of 236 total samples (100.0%) in interval 2, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 239 samples with unknown uncertainty out of 239 total samples (100.0%) in interval 3, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 239 samples with unknown uncertainty out of 239 total samples (100.0%) in interval 4, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 238 samples with unknown uncertainty out of 238 total samples (100.0%) in interval 5, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 6, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 7, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 235 samples with unknown uncertainty out of 235 total samples (100.0%) in interval 8, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 239 samples with unknown uncertainty out of 239 total samples (100.0%) in interval 9, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 10, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 238 samples with unknown uncertainty out of 238 total samples (100.0%) in interval 11, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 238 samples with unknown uncertainty out of 238 total samples (100.0%) in interval 12, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 237 samples with unknown uncertainty out of 237 total samples (100.0%) in interval 13, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
Benchmark Results Summary
Target Load Average Active Power (W) Minimum Ambient Temperature (°C)
Calibration 1 48.5 22.2
Calibration 2 48.9 22.2
Calibration 3 49.3 22.3
100% 49.3 22.4
90% 50.8 22.4
80% 50.3 22.4
70% 48.3 22.5
60% 45.3 22.5
50% 41.1 22.6
40% 35.7 22.6
30% 29.6 22.6
20% 23.8 22.6
10% 19.5 22.7
Active Idle 15.4 22.7
Graph of power and temperature
Measurement Devices
Power Analyzer pwr1
Hardware Vendor: Hioki
Model: 3334
Serial Number: 150526689
Connectivity: USB
Input Connection: Default
Metrology Institute: NIST
Accredited by: Hioki
Calibration Label: Unknown
Date of Calibration: Unknown
PTDaemon Host System: same as CCS
PTDaemon Host OS: same as CCS
PTDaemon Version: 1.8.0-3505e615-20160120
Setup Description: Unknown
Temperature Sensor temp1
Hardware Vendor: Digi
Model: Watchport H/T Sensor
Driver Version: io_ti 3.16.0-4-amd64
Connectivity: USB
PTDaemon Host System: same as CCS
PTDaemon Host OS: same as CCS
Setup Description: 5mm in front of SUT
Notes
None
Power Details for Device pwr1
Target Load Voltage (V) Current (A) Avg Power Factor Avg Active Power (W) Power Measurement Uncertainty (%)
Avg Range Avg Range
Calibration 1 118 auto 0.417 auto 0.983 48.5 --
Calibration 2 119 auto 0.417 auto 0.983 48.9 --
Calibration 3 120 auto 0.418 auto 0.983 49.3 --
100% 120 auto 0.417 auto 0.983 49.3 --
90% 120 auto 0.434 auto 0.974 50.8 --
80% 120 auto 0.435 auto 0.964 50.3 --
70% 120 auto 0.424 auto 0.951 48.3 --
60% 119 auto 0.408 auto 0.937 45.3 --
50% 118 auto 0.378 auto 0.922 41.1 --
40% 119 auto 0.333 auto 0.907 35.7 --
30% 120 auto 0.279 auto 0.895 29.6 --
20% 120 auto 0.224 auto 0.895 23.8 --
10% 120 auto 0.183 auto 0.891 19.5 --
Active Idle 120 auto 0.141 auto 0.904 15.4 --