Low Power Company, Inc. LP-4290 SPECpower_ssj2008 = Invalid overall ssj_ops/watt
Test Sponsor: Low Power Company, Inc. SPEC License #: 4777 Test Method: Single Node
Tested By: Low Power Company, Inc. Test Location: Mountain View, CA Test Date: Apr 19, 2017
Hardware Availability: March 2017 Software Availability: Mar-2017 Publication: Unpublished
System Source: Low Power Company, Inc. System Designation: LP-4290-8H Power Provisioning: Line-powered
WARNING: PTDaemon 1.8.0-3505e615-20160120 is over 12 months old. Check http://www.spec.org/power/docs/SPECpower-Device_List.html to determine if a newer version is available. (see Run Rules Section 1.1)
WARNING: PTDaemon 1.8.0-3505e615-20160120 is over 12 months old. Check http://www.spec.org/power/docs/SPECpower-Device_List.html to determine if a newer version is available. (see Run Rules Section 1.1)
INVALID: Power Analyzer "pwr1" had 77.7% bad watt readings in interval 9, exceeding threshold of 1.0% (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 77.7% bad amp readings in interval 9, exceeding threshold of 2.0% (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 52.1% bad power factor readings in interval 9, exceeding threshold of 2.0% (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 11.8% bad watt readings in interval 10, exceeding threshold of 1.0% (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 11.8% bad amp readings in interval 10, exceeding threshold of 2.0% (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 11.8% bad power factor readings in interval 10, exceeding threshold of 2.0% (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 184 samples with unknown uncertainty out of 237 total samples (77.6%) in interval 9, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
INVALID: Power Analyzer "pwr1" had 28 samples with unknown uncertainty out of 238 total samples (11.8%) in interval 10, exceeding the threshold of 1.0%. (see Run Rules Section 2.5.2)
Benchmark Results Summary
Target Load Average Active Power (W) Minimum Ambient Temperature (°C)
Calibration 1 46.9 23.5
Calibration 2 47.2 23.5
Calibration 3 47.4 23.5
100% 47.4 23.6
90% 49.2 23.6
80% 48.7 23.6
70% 46.8 23.6
60% 43.9 23.6
50% 39.6 23.6
40% 31.9 23.6
30% 28.0 23.7
20% 22.4 23.8
10% 17.8 23.8
Active Idle 13.6 23.8
Graph of power and temperature
Measurement Devices
Power Analyzer pwr1
Hardware Vendor: Hioki
Model: 3334
Serial Number: 150526689
Connectivity: USB
Input Connection: Default
Metrology Institute: NIST
Accredited by: Hioki
Calibration Label: N-3650
Date of Calibration: 8-Jun-2009
PTDaemon Host System: same as CCS
PTDaemon Host OS: same as CCS
PTDaemon Version: 1.8.0-3505e615-20160120
Setup Description: Unknown
Temperature Sensor temp1
Hardware Vendor: Digi
Model: Watchport H/T Sensor
Driver Version: io_ti 3.16.0-4-amd64
Connectivity: USB
PTDaemon Host System: same as CCS
PTDaemon Host OS: same as CCS
Setup Description: 5mm in front of SUT
Notes
None
Power Details for Device pwr1
Target Load Voltage (V) Current (A) Avg Power Factor Avg Active Power (W) Power Measurement Uncertainty (%)
Avg Range Avg Range
Calibration 1 120 150.0 0.399 1.0 0.982 46.9 0.5%
Calibration 2 119 150.0 0.403 1.0 0.982 47.2 0.5%
Calibration 3 119 150.0 0.405 1.0 0.982 47.4 0.5%
100% 119 150.0 0.406 1.0 0.983 47.4 0.5%
90% 119 150.0 0.425 1.0 0.973 49.2 0.5%
80% 119 150.0 0.427 1.0 0.960 48.7 0.5%
70% 119 150.0 0.416 1.0 0.946 46.8 0.5%
60% 119 150.0 0.397 1.0 0.931 43.9 0.5%
50% 119 150.0 0.364 1.0 0.916 39.6 0.6%
40% 119 150.0 0.299 0.3 0.897 31.9 0.3%
30% 120 150.0 0.264 0.3 0.885 28.0 0.3%
20% 120 150.0 0.214 0.3 0.876 22.4 0.4%
10% 120 150.0 0.171 0.3 0.868 17.8 0.5%
Active Idle 120 150.0 0.128 0.3 0.886 13.6 0.6%
Power details for pwr1