Low Power Company, Inc. Lopoco LP-4290 Series Server SPECpower_ssj2008 = 6,486 overall ssj_ops/watt
Test Sponsor: Low Power Company, Inc. SPEC License #: 4777 Test Method: Single Node
Tested By: Low Power Company, Inc. Test Location: Mountain View, CA Test Date: May 2, 2017
Hardware Availability: January 2017 Software Availability: Jan-2017 Publication: Unpublished
System Source: Low Power Company, Inc. System Designation: LP-4290-2I Power Provisioning: Line-powered
WARNING: PTDaemon 1.8.0-3505e615-20160120 is over 12 months old. Check http://www.spec.org/power/docs/SPECpower-Device_List.html to determine if a newer version is available. (see Run Rules Section 1.1)
WARNING: PTDaemon 1.8.0-3505e615-20160120 is over 12 months old. Check http://www.spec.org/power/docs/SPECpower-Device_List.html to determine if a newer version is available. (see Run Rules Section 1.1)
WARNING: Power Analyzer "pwr1" had 1 samples with uncertainty exceeding 1.0% out of 238 total samples (0.4%) in interval 10.
Benchmark Results Summary
Target Load Average Active Power (W) Minimum Ambient Temperature (°C)
Calibration 1 44.4 28.5
Calibration 2 44.6 28.6
Calibration 3 44.9 28.6
100% 44.9 28.7
90% 41.6 28.4
80% 38.4 28.2
70% 35.4 28.1
60% 32.4 28.0
50% 29.3 27.9
40% 26.0 27.8
30% 22.5 27.7
20% 18.7 27.6
10% 14.6 27.6
Active Idle 10.1 27.4
Graph of power and temperature
Measurement Devices
Power Analyzer pwr1
Hardware Vendor: Hioki
Model: 3334
Serial Number: 150526689
Connectivity: USB
Input Connection: Default
Metrology Institute: NIST
Accredited by: Hioki
Calibration Label: N-3650
Date of Calibration: 8-Jun-2009
PTDaemon Host System: same as CCS
PTDaemon Host OS: same as CCS
PTDaemon Version: 1.8.0-3505e615-20160120
Setup Description: Unknown
Temperature Sensor temp1
Hardware Vendor: Digi
Model: Watchport H/T Sensor
Driver Version: io_ti 3.16.0-4-amd64
Connectivity: USB
PTDaemon Host System: same as CCS
PTDaemon Host OS: same as CCS
Setup Description: 5mm in front of SUT
Notes
None
Power Details for Device pwr1
Target Load Voltage (V) Current (A) Avg Power Factor Avg Active Power (W) Power Measurement Uncertainty (%)
Avg Range Avg Range
Calibration 1 120 150.0 0.377 1.0 0.980 44.4 0.5%
Calibration 2 120 150.0 0.380 1.0 0.981 44.6 0.5%
Calibration 3 118 150.0 0.387 1.0 0.982 44.9 0.5%
100% 119 150.0 0.385 1.0 0.982 44.9 0.5%
90% 119 150.0 0.358 1.0 0.975 41.6 0.5%
80% 119 150.0 0.335 1.0 0.967 38.4 0.6%
70% 119 150.0 0.311 1.0 0.956 35.4 0.6%
60% 118 150.0 0.289 1.0 0.946 32.4 0.6%
50% 117 150.0 0.267 1.0 0.933 29.3 0.7%
40% 118 150.0 0.241 1.0 0.916 26.0 0.8%
30% 118 150.0 0.213 1.0 0.896 22.5 0.9%
20% 118 150.0 0.181 0.3 0.876 18.7 0.5%
10% 118 150.0 0.144 0.3 0.854 14.6 0.6%
Active Idle 118 150.0 0.101 0.3 0.847 10.1 0.7%
Power details for pwr1